ControlBox
TB-216 Web Server
Modbus configuration

Note: All registers are in 'big-Endian' format

Enable slave
 
Address table for 03 Read Holding Registers function
AddressParameterTypeSizeValue
0TemperatureFloat2-50.0 ... 125.0
Int16*1-500 ... 1250
Int161-50 ... 125
2StateInt1610,1,2,3**
3Alert minInt161-50 ... 125
4Alert maxInt161-50 ... 125
5Warning minInt161-50 ... 125
6Warning maxInt161-50 ... 125
7Critical minInt161-50 ... 125
8Critical maxInt161-50 ... 125
9Device IDInt322Device ID
* to preserve accuracy, the value is calculated as Temperature*10
** 0 - Normal, 1 - Alert, 2 - Warning, 3 - Critical